2-TON CHILLERS MADE IN THE USA

2 Ton Water Chillers

Cold Shot Chillers 2 Ton model ACWC-24-Q water chillers are made in the USA and are among the most durable and dependable chillers on the market. We offer 2 Ton chillers in air-cooled or water-cooled configurations. Stationary, portable, and reverse flow designs are available to accommodate virtually any heat removal application.

2 Ton Air-cooled Chiller (Portable)

This unit features a hermetic scroll compressor and R410A refrigerant for effective and reliable cooling. The chiller is controlled and monitored through an onboard PLC. Temperature control setting is performed on an easy to read and operate LED temperature controller. Safeties are built into the chiller to protect the unit from adverse conditions associated with normal wear and tear. All alerts and notifications are monitored through the PLC to display an error code should one occur.

The term “portable” refers to the basic configuration of the system, not to its mobility. Most portable chiller units will never be moved once installed. The term refers to any chiller system that contains the necessary components such as the refrigeration circuit, the reservoir, and the pump or pumps, within a single footprint.

The unit weighs approximately 563 lbs. in total with dimensions of 42” L x 32 ½” W x 51 ½” H.

Standard Features

Controls: The unit comes standard with an electronic programmed temperature controller with constant (set point & process) temperature readout.

Refrigeration Components: Efficient scroll compressors, balanced port expansion valves, sight glass/moisture indicators, pump down valves, filter drier, fan cycling head pressure controls.

Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal. Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a bypass flow valve.

Safety Controls: High and low refrigerant pressure, high and low fluid temperature, low water flow, thermal overloads for compressor and fan motors, safety fuses or overloads for pump.

Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.

Warranty: One year for parts / five year for the compressor.

2 Ton Air-cooled Chiller (Stationary)

The term “stationary” refers to any chiller that does not include a pump or a tank. The main component is a stand-alone chiller unit that must be connected by piping to a pump and a separate reservoir to function properly.

Our 2 Ton model ACWC-25-QST typically have separate controls for the chiller and the pump, with an electrical connection for each component. The controls should ideally be wired together, to prevent the chiller from cooling until the circulating pump is operating. 

This chiller features a single stage hermetic scroll compressor. We use R410A refrigerant which is an environmentally friendly refrigerant for effective and reliable cooling. Non-ferrous metal such as stainless steel and copper are used for all fluid contact parts. The chiller tank, evaporator, and centrifugal pump are stainless steel. The piping used on the chiller is copper.

The unit weighs approximately 550 lbs. with dimensions of 42” L x 32 ½” W x 51 ½” H.

Standard Features

Controls: The unit comes standard with an electronic programmed temperature controller with constant (set point & process) temperature readout.

Refrigeration Components: Efficient scroll compressors, balanced port expansion valves, sight glass/moisture indicators, pump down valves, filter drier, fan cycling head pressure controls.

Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen.

Safety Controls: High and low refrigerant pressure, high and low fluid temperature, low water flow, thermal overloads for compressor and fan motors.

Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.

Warranty: One year for parts / five year for the compressor. 

2 Ton Air-cooled Chiller (Reverse Flow)

The term “reverse flow” refers to a chiller that includes the refrigeration circuit, evaporator, and pump. The chiller is usually located near the customer’s external tank. Many of these applications are to chill an external tank to a predetermined temperature setting. The fluid is then pumped out to the customer’s process to remove heat from equipment. The warmed fluid is then pumped back to the external tank where the heat is exchanged by the chiller. 

The 2 Ton model ACWC-24-QRF weighs approximately 550 lbs. in total with dimensions of 42” L x 32 ½” W x 51 ½” H.

Standard Features

Controls: The unit comes standard with an electronic programmed temperature controller with constant (set point & process) temperature readout.

Refrigeration Components: Efficient scroll compressors, balanced port expansion valves, sight glass/moisture indicators, pump down valves, filter drier, fan cycling head pressure controls.

Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal.

Safety Controls: High and low refrigerant pressure, high and low fluid temperature, low water flow, thermal overloads for compressor and fan motors, safety fuses or overloads for pump.

Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.

Warranty: One year for parts / five year for the compressor.

2 Ton Water-cooled Units (Portable)

Our 2 Ton model WCWC-24-Q is a portable water-cooled water chiller capable of removing up to 24,000 BTU/Hr. with a 50°F leaving fluid temperature with a condensing water temperature of 85°F.

The chiller puts off relatively little heat and is commonly located indoors near the process it is removing heat from. The condensing water can be from a building chilled water supply, pond, lake, or geothermal.

A common and readily available R-410A refrigerant is used due to its non-depleting ozone characteristics. We use a single stage hermetic scroll compressor to provide a wide range of temperature settings to accommodate precise heat removal from your process.

The dry weight of the 2 Ton model WCWC-24-E is approximately 350 lbs. This portable chiller has dimensions of 41” L x 29” W x 52” H and is built with long-lasting performance in mind.

Standard Features

Controls: Electronic programmed temp. controller with a constant (set point & process) temperature readout.

Refrigeration Components: Efficient scroll compressors, sight glass/moisture indicators, balanced port expansion valves, filter drier, access ports and or service valves, pressure actuated head pressure controls, liquid receiver.

Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal. Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a bypass flow valve.

Safety Controls: High and low refrigerant pressure controls, high and low fluid temperature, low water flow, thermal overloads for compressors, safety fuses or overloads for pump.

Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.

Warranty: One year parts / five year compressor.

2 Ton Water-cooled Chillers (Reverse Flow)

Cold Shot Chillers reverse flow chillers do not include tanks due to their use of an open loop cooling system. For applications of these types, an external tank is used to provide positive head pressure of water or heat transfer fluid to the system’s pump. The fluid is pumped from the external tank to the chiller and back to the tank. The heat from the fluid is transferred through the chiller’s evaporator, though the refrigerant circuit and to the water condensing heat evaporator. 

Standard Features

Controls: Electronic programmed temperature controller with constant (set point & process) temperature readout.

Refrigeration Components: Efficient scroll compressors, sight glass/moisture indicators, balanced port expansion valves, filter drier, access ports and or service valves, pressure actuated head pressure controls, liquid receiver.

Process Fluid Components: Bronze “Y” strainer with 20 mesh stainless steel screen. Pumps are stainless steel centrifugal. Tanks are insulated with shoe box lid, fill port, and level sight glass. Portable systems will include a bypass flow valve.

Safety Controls: High and low refrigerant pressure, high and low fluid temperature, low water flow, thermal overloads for compressors, safety fuses or overloads for pump.

Construction: Welded steel powder coated frame and full metal cabinet, copper piping connections.

Warranty: One year parts / five year compressor.

2 Ton Chiller Specifications

Model #TypeStyleCapacityVoltagePump HP + Flow RateConnections
ACWC-24-QAir-cooledPortable24,000 BTU/HR*208-230/1/601HP 30gpm@30psi1” MNPT IN/OUT
ACWC-24-Q-STAir-cooledStationary24,000 BTU/HR*208-230/1/60N/A1” MNPT IN/OUT
ACWC-24-Q-RFAir-cooledReverse Flow24,000 BTU/HR*208-230/1/601HP 30gpm@30psi1” MNPT IN/OUT
WCWC-24-EWater-cooledPortable24,000 BTU/HR**208-230/1/601HP 30gpm@30psi1” MNPT IN/OUT
WCWC-24-E-STWater-cooledStationary24,000 BTU/HR**208-230/1/60N/A1” MNPT IN/OUT
WCWC-24-E-RFWater-cooledReverse Flow24,000 BTU/HR**208-230/1/601HP 30gpm@30psi1” MNPT IN/OUT

* Capacity- 50°F LCWT/95°F AMB
** Capacity- 50°F LCWT/85°F CWT

Note: All specifications subject to change without notice. Specify Voltage and Ambient Condition upon ordering.