3-Ton Chiller Units

3 Ton Water Chillers Made in the USA

Cold Shot Chillers’ 3-ton units are made in the USA and built for industrial process cooling applications. These air- and water-cooled chillers feature precise temperature control from 20°F to 70°F and are available in portable, stationary, and reverse flow setups. Digital water pressure display, visual alarms, and optional communications upgrades are available.

Air-Cooled Chillers

Portable (ACWC-36-Q)

Our 3 ton air cooled portable chillers include a digital scroll compressor and R410A refrigerant. Fully integrated internal pumping system and stainless steel reservoir with bypass valve. Induced air flow design maximizes heat transfer.

Unit Cooling Capacity: 36,000 BTU/hr (3 tons capacity)

Approximate Unit Weight (crated): Approx. 571 lbs.

Size: 42”L x 32.5”W x 52.5”H

Features:

  1. Temp controller (set point + readout)
  2. Hot gas bypass controls for precise temperature management
  3. Filter drier, sight glass
  4. Air cooled air flow design
  5. Audible signal industry-standard alarms
  6. Warranty: 1 yr parts / 5 yrs compressor

Stationary (ACWC-36-QST)

This 3 ton air-cooled stationary model has no pump or tank; connects to external systems. Meant for outdoor or indoor ambient air environments.

Approximate Unit Weight (crated): 500 lbs.

Size: 42”L x 32.5”W x 51.5”H

Same cooling and safety features

Reverse Flow (ACWC-36-QRF)

The 3 ton air cooled reverse flow chiller includes no internal tank; placed near external reservoir for positive head pressure.

Weight (crated): 550 lbs.

Size: 42”L x 32.5”W x 51.5”H

Same controls, cooling capacity, and stainless pump

Water-Cooled Chillers

Portable (WCWC-36-E)

Indoor-friendly unit with low noise and reduced ambient temperatures. Portable chillers work with geothermal or cooling tower.

Unit Cooling Capacity: 36,000 BTU/hr

Stainless Steel Reservoir Capacity: 25 gallons

Weight (crated): 420 lbs.

Size: 41”L x 29”W x 53”H

Features:

  1. Scroll compressor, digital temp control
  2. Visual alarms, stainless steel fluid path
  3. All non-ferrous materials for clean closed-loop
  4. Optional process connections available

Reverse Flow (WCWC-36-ERF)

Requires two water sources: one for chilling, one for heat removal. Ideal for mixing, agriculture, and consistent chiller capacity.

  1. Same size and weight as Portable
  2. Same controls, pumps, and optional upgrades

3-Ton Chiller Technical Specifications

Model #TypeStyleCapacityVoltagePump HP + Flow RateConnections
ACWC-36-QAir-cooledPortable36,000 BTU/HR*208-230/1/60208-230/3/60460/3/601HP 30gpm@30psi1” MNPT IN/OUT
ACWC-36-Q-STAir-cooledStationary36,000 BTU/HR*208-230/1/60208-230/3/60460/3/60N/A1” MNPT IN/OUT
ACWC-36-Q-RFAir-cooledReverse Flow36,000 BTU/HR*208-230/1/60208-230/3/60460/3/601HP 30gpm@30psi1 1/4” MNPT IN/ 1”OUT
WCWC-36-EWater-cooledPortable36,000 BTU/HR**208-230/1/60208-230/3/60460/3/601HP 30gpm@30psi1” MNPT IN/OUT
WCWC-36-E-STWater-cooledStationary36,000 BTU/HR**208-230/1/60208-230/3/60460/3/60N/A1” MNPT IN/OUT
WCWC-36-E-RFWater-cooledReverse Flow36,000 BTU/HR**208-230/1/60208-230/3/60460/3/601HP 30gpm@30psi1” MNPT IN/OUT

* Capacity- 50°F LCWT/95°F AMB
** Capacity- 50°F LCWT/85°F CWT

Note: All specifications are subject to change without notice. Specify Voltage and Ambient Condition upon ordering.

Loading & Operation

  1. Minimum Recommended Operating Temperature: 20°F leaving water temp
  2. Loading Specifications Model: Available upon request
  3. Actual Unit Appearance: May vary slightly; refer to product literature for details

Support & Documentation

  1. Full feature support documents, manuals, and technical specifications available
  2. Optional upgrades: digital readouts, alarms, remote comms, and process fittings

3-Ton Chiller Pricing

Price starting as low as $9,112.00

FAQs

What are 3-ton water chillers used for?

A 3-ton water chiller can cool plastic processing equipment, laser and welding systems, CNC machines, lab equipment, printing machinery, small tanks, and process fluid loops. The right model depends on the cooling load, flow rate, target fluid temperature, and site conditions.

How do I choose between an air-cooled and water-cooled 3-ton chiller?

Air-cooled chillers reject heat into the surrounding air and do not require a condenser-water system. Water-cooled chillers require a cooling tower, geothermal loop, or another source of condenser water. The best option depends on installation space, ambient conditions, available utilities, and heat-rejection needs.

Is a 3-ton chiller equal to 3 horsepower?

No. Chiller tonnage measures cooling capacity, while horsepower measures motor power. A 3-ton chiller provides approximately 36,000 BTU/hr under its rated operating conditions. Its compressor and pump may have different horsepower ratings.

What maintenance does a 3-ton chiller require?

Maintenance may include cleaning the Y-strainer and condenser, checking fluid and glycol levels, inspecting electrical connections, and checking for leaks. The schedule depends on the model, operating hours, fluid, and site conditions.

Contact Cold Shot Chillers Today

Need a quote fast? Looking for the right system for your process? We offer expert help and quick shipping on all models, including top-performing 3 ton air cooled chillers and compact portable chillers. Add options like capacity control alarm output, hot gas bypass controls, and custom connections to match your exact specs.

Our team will help with sizing, setup, and specs – plus full support and docs for every chiller. Contact us now for immediate factory pricing and details on your ideal system.

Request a Quote

Request a Quote (Footer Form)

Request a Quote

Max. file size: 8 MB.